TECK90 (XLPE) 600 Volts -40°C Copper

10AWG Multi-Conductor

 

 

ASTM Class B stranded soft bare copper. In sizes 8 AWG to 1000 kcmil, the conductors are compact stranded to reduce cable diameter and weight. Insulation is cross-linked polyethylene XLPE, the most widely used polymeric material for insulating both low and high voltage cables. The insulated conductors in the unshielded TECK cables rated 5 KV or less meet the requirement of CSA for RW90 XLPE.

Packaging: Long length Reels, cut to length.

Construction & Technical Data

Connector Selection Chart

ECS
Catalogue
Number
Conductor Bonding Conductor Insulation
(inches)
Inner Jacket
(inches)

Approximate Diameters

Ampacity Total
Weight
(lbs/km)
No. AWG
Size
Inner Jacket  Armour Outer Covering
TK10-02 2 10 12 .030 .045 .450 .630 .721 30 892
TK10-03 3 10 12 .030 .045 .480 .660 .751 30 1,112
TK10-04 4 10 12 .030 .045 .541 .721 .810 30 1,256
TK10-05 5 10 12 .030 .060 .630 .831 .921 30 1,381
TK10-06 6 10 12 .030 .060 .691 .891 .981 30 1,696
TK10-07 7 10 12 .030 .060 .691 .891 .981 30 1,768
TK10-08 8 10 12 .030 .060 .741 .941 1.041 30 2,024
TK10-09 9 10 12 .030 .060 .810 1.031 1.121 30 2,076
TK10-10 10 10 12 .030 .060 .841 1.061 1.151 30 2,546
TK10-11 11 10 12 .030 .060 .841 1.061 1.151 30 2,608
TK10-12 12 10 12 .030 .080 .901 1.121 1.221 30 2,903
TK10-15 15 10 12 .030 .080 1.001 1.221 1.311 30 3,465
TK10-19 19 10 12 .030 .080 1.051 1.271 1.371 30 3,967
TK10-20 20 10 12 .030 .080 1.121 1.341 1.431 30 4,235
TK10-25 25 10 12 .030 .080 1.251 1.471 1.561 30 5,013
TK10-30 30 10 12 .030 .080 1.321 1.541 1.631 30 5,807
TK10-37 37 10 12 .030 .080 1.421 1.641 1.751 30 6,880
TK10-40 40 10 12 .030 .080 1.481 1.701 1.811 30 7,539
TK10-50 50 10 12 .030 .080 1.681 1.931 2.042 30 9,000
TK10-60 60 10 12 .030 .110 1.910 2.260 2.314 30 10,837
TK10-80 80 10 12 .030 .110 2.133 2.483 2.570 30 13,862
TK10-90 90 10 12 .030 .110 2.246 2.596 2.683 30 15,276